In some installations the wire tray needs to be equipotentially bonded. This is to secure protective bonding or functional bonding.


Protective bonding 
The main reason for protection bonding is to protect against electrical shock that could be caused by faults in the electrical system. This is remedied by connecting the wire tray to the main earth terminal in the building.

Functional bonding
This is done to minimise the impact of electrical and magnetic fields (EMC). It is carried out in the same way as with protective bonding, i.e. by connecting the wire tray to the main earth terminal in the building.

Requirements and tests
The IEC 61537 standard lays down the requirements placed on a wire tray to ensure electrical continuity. Among other things, the impedance must not exceed 50 mOhm over joints or 5 mOhm X number of meters of wire tray. 

X-Tray has been tested and complies fully with IEC 61537. The tests were conducted by the Research Institute of Sweden (SP) with test report numbers PX16030 and 5F015879.

 

NB. X-Tray wire trays must never be used as protective bonding conductors, earth conductors or any other type of protective conductor. 

Read more about Equipotential bonding here!

Axelent Xperience

Visit our virtual showroom and experience our products in their right environment.

In our virtual showroom, you get to experience Axelent's range in its right environment, no matter where in the world you are. Explore our products by navigating between production, storage, warehousing, automated warehouse and dispatch. If something special catches your interest, just click on the product to find out more. Watch a movie, read an article and learn more! We think you will like it as much as we do!